Computational fluid dynamics modeling of flammable refrigerant leaks inside machine rooms: Evaluation of ventilation mitigation requirements. (18th May 2016)
- Record Type:
- Journal Article
- Title:
- Computational fluid dynamics modeling of flammable refrigerant leaks inside machine rooms: Evaluation of ventilation mitigation requirements. (18th May 2016)
- Main Title:
- Computational fluid dynamics modeling of flammable refrigerant leaks inside machine rooms: Evaluation of ventilation mitigation requirements
- Authors:
- Papas, Paul
Zhang, Shiling
Jiang, Hai
Verma, Parmesh
Rydkin, Ivan
Lord, Richard
Burns, Larry - Abstract:
- Abstract : Computational fluid dynamics simulations were undertaken to quantify ventilation dilution requirements needed for mitigating flammability risks during leaks of flammable refrigerants from large chillers inside machine rooms. Machine rooms ranging in size from 376 to 2256 m 3 were modeled using computational fluid dynamics to simulate major leaks from a 2640 kW (750TR) chiller. As is required by existing safety standards, a refrigerant sensor was incorporated to trigger and activate an alarm or emergency level ventilation system to dilute the room with fresh air. A range of refrigerant leak rates and different alarm-triggered ventilation rates were evaluated to understand dilution requirements to prevent significant flammable mass accumulation. To verify the computational fluid dynamics findings, verification testing was also conducted in a 574 m 3 machine room setup using carbon dioxide as a surrogate refrigerant. When matching volumetric leak rates, computational fluid dynamics results were comparable with verification testing data. These results will be discussed in light of current machine room ventilation standards and used to establish a relationship for the alarm ventilation rate needed for mitigating risks for major refrigerant leaks inside machine rooms.
- Is Part Of:
- Science and technology for the built environment. Volume 22:Number 4(2016)
- Journal:
- Science and technology for the built environment
- Issue:
- Volume 22:Number 4(2016)
- Issue Display:
- Volume 22, Issue 4 (2016)
- Year:
- 2016
- Volume:
- 22
- Issue:
- 4
- Issue Sort Value:
- 2016-0022-0004-0000
- Page Start:
- 463
- Page End:
- 471
- Publication Date:
- 2016-05-18
- Subjects:
- Heating -- Periodicals
Ventilation -- Periodicals
Air conditioning -- Periodicals
Refrigeration and refrigerating machinery -- Periodicals
Indoor air quality -- Periodicals
Indoor air quality
Air conditioning
Heating
Refrigeration and refrigerating machinery
Ventilation
Periodicals
697 - Journal URLs:
- http://www.tandfonline.com/loi/uhvc21#.VfchsBHBzRY ↗
http://www.tandfonline.com/ ↗ - DOI:
- 10.1080/23744731.2016.1163240 ↗
- Languages:
- English
- ISSNs:
- 2374-474X
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 1921.xml