Airflow patterns due to door motion and pressurization in hospital isolation rooms. (18th May 2016)
- Record Type:
- Journal Article
- Title:
- Airflow patterns due to door motion and pressurization in hospital isolation rooms. (18th May 2016)
- Main Title:
- Airflow patterns due to door motion and pressurization in hospital isolation rooms
- Authors:
- Mousavi, Ehsan S.
Grosskopf, Kevin R. - Abstract:
- Abstract : Certain pathogens are transmitted through air by respiratory droplets that desiccate shortly after emission and form droplet nuclei (Nicas et al. 2005). Droplet nuclei are sufficiently small (<5.0 μm) to remain suspended in air indefinitely and, thus, create a pathway between an infected and susceptible person (Sehulster et al. 2003). This process is called "airborne transmission." Patients with an airborne infectious disease (e.g., measles, SARS, tuberculosis, varicella, etc.) are isolated from the healthcare environment in an airborne infection isolation room to protect other patients and healthcare workers. These rooms have special features to effectively contain and remove airborne pathogens. For example, a 2.5-Pa negative pressure relationship with adjoining spaces is required for an airborne infection isolation room to create directional airflow into the room and prevent the transmission of airborne pathogens from the airborne infection isolation room to adjacent healthcare spaces. Directional airflow, however, may be disrupted and even reversed by door-opening motion and the movement of people and equipment into and out of the airborne infection isolation room. This article highlights the results of both experimental and computation studies that explore air exchange and particle movement between an isolation room and anteroom relative to 3-, 5-, and 7-s door cycle speeds and between neutral and negative air pressure relationships.
- Is Part Of:
- Science and technology for the built environment. Volume 22:Number 4(2016)
- Journal:
- Science and technology for the built environment
- Issue:
- Volume 22:Number 4(2016)
- Issue Display:
- Volume 22, Issue 4 (2016)
- Year:
- 2016
- Volume:
- 22
- Issue:
- 4
- Issue Sort Value:
- 2016-0022-0004-0000
- Page Start:
- 379
- Page End:
- 384
- Publication Date:
- 2016-05-18
- Subjects:
- Heating -- Periodicals
Ventilation -- Periodicals
Air conditioning -- Periodicals
Refrigeration and refrigerating machinery -- Periodicals
Indoor air quality -- Periodicals
Indoor air quality
Air conditioning
Heating
Refrigeration and refrigerating machinery
Ventilation
Periodicals
697 - Journal URLs:
- http://www.tandfonline.com/loi/uhvc21#.VfchsBHBzRY ↗
http://www.tandfonline.com/ ↗ - DOI:
- 10.1080/23744731.2016.1155959 ↗
- Languages:
- English
- ISSNs:
- 2374-474X
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 1921.xml