Energy and environmental performance assessment of R744 booster supermarket refrigeration systems operating in warm climates. (April 2016)
- Record Type:
- Journal Article
- Title:
- Energy and environmental performance assessment of R744 booster supermarket refrigeration systems operating in warm climates. (April 2016)
- Main Title:
- Energy and environmental performance assessment of R744 booster supermarket refrigeration systems operating in warm climates
- Authors:
- Gullo, Paride
Elmegaard, Brian
Cortella, Giovanni - Abstract:
- Highlights: Annual energy consumption of different R744 refrigeration plants is compared. Two different warm locations are taken into account. Use of dedicated mechanical subcooling allows reducing energy consumption markedly. Parallel compression is more convenient for external temperatures up to 33 °C. All the enhanced R744 booster systems lead to a substantial reduction in TEWI. Abstract: This paper presents a theoretical comparison among different commercial refrigeration systems in terms of annual energy consumption and environmental impact. Eight configurations were studied: a R744/R134a cascade refrigeration system (baseline), a conventional and an improved R744 booster system, two R744 booster solutions with dedicated mechanical subcooling, a R744 booster with parallel compression and two solutions which combined the parallel compression and the mechanical subcooling. The evaluation was based on the weather data in Valencia (Spain) and in Athens (Greece), as well as on the running modes of a conventional European supermarket. A transition zone, which occurred between subcritical and transcritical operations, was adopted. The results showed that all the enhanced configurations may achieve a comparable energy saving to the one of the baseline in both the selected locations. Furthermore, they allow reducing the Total Equivalent Warming Impact (TEWI) by at least 9.6% beside the cascade solution.
- Is Part Of:
- International journal of refrigeration. Volume 64(2016:Apr.)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 64(2016:Apr.)
- Issue Display:
- Volume 64 (2016)
- Year:
- 2016
- Volume:
- 64
- Issue Sort Value:
- 2016-0064-0000-0000
- Page Start:
- 61
- Page End:
- 79
- Publication Date:
- 2016-04
- Subjects:
- Annual energy consumption -- CO2 -- Compressor efficiency -- Dedicated mechanical subcooling -- Parallel compression -- TEWI
Consommation énergétique annuelle -- CO2 -- Rendement du compresseur -- Sous refroidissement mécanique dédié -- Compression parallèle -- TEWI
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2015.12.016 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 1213.xml