Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system. (December 2015)
- Record Type:
- Journal Article
- Title:
- Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system. (December 2015)
- Main Title:
- Testing, simulation and soft-optimization of R410A low-GWP alternatives in heat pump system
- Authors:
- Alabdulkarem, Abdullah
Eldeeb, Radia
Hwang, Yunho
Aute, Vikrant
Radermacher, Reinhard - Abstract:
- Highlights: Drop-in tests of three R410A low-GWP alternative refrigerants were performed. The results show that R32 and L41a are good replacement candidates for R410A. Most of the predicted COP and capacity results of R32 experiments agree with the measured values. Varying the compressor size and adding a suction line heat exchanger to the system were investigated. Abstract: The environmental impact of high global warming potential (GWP) refrigerants pushed the HVAC&R industry to investigate alternative refrigerants. R410A is a common refrigerant for air conditioning and heat pumping applications, but has a GWP of 2088. Drop-in tests of three R410A low-GWP alternative refrigerants (R32, D2Y60 and L41a) in a 10.55 kW capacity split heat pump unit were performed. The results show that R32 and L41a are good replacement candidates for R410A. A finite volume heat exchanger model and component based vapor compression system simulation tools were validated against the experimental data. Most of the predicted COP and capacity results of R32 experiments lie within 5% of the measured values, which is in good agreement with the experiments. Further investigation was carried out by varying the size of the compressor and adding a suction line heat exchanger to the system to match the capacity to that of R410A.
- Is Part Of:
- International journal of refrigeration. Volume 60(2015:Dec.)
- Journal:
- International journal of refrigeration
- Issue:
- Volume 60(2015:Dec.)
- Issue Display:
- Volume 60 (2015)
- Year:
- 2015
- Volume:
- 60
- Issue Sort Value:
- 2015-0060-0000-0000
- Page Start:
- 106
- Page End:
- 117
- Publication Date:
- 2015-12
- Subjects:
- R410A -- Heat pumps -- AREP -- Alternative lower GWP refrigerants -- Compressor size -- Suction line heat exchanger
R410A -- Pompes à chaleur -- AREP -- Frigorigènes alternatifs à faible GWP -- Taille de compresseur -- Echangeur de chaleur de la ligne d'aspiration
Refrigeration and refrigerating machinery -- Periodicals
621.56 - Journal URLs:
- http://www.elsevier.com/journals ↗
http://www.sciencedirect.com/science/journal/aip/01407007 ↗ - DOI:
- 10.1016/j.ijrefrig.2015.08.001 ↗
- Languages:
- English
- ISSNs:
- 0140-7007
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 4542.525500
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File: