Optimum design of horizontal ground-coupled heat pump systems using spiral-coil-loop heat exchangers. (15th January 2016)
- Record Type:
- Journal Article
- Title:
- Optimum design of horizontal ground-coupled heat pump systems using spiral-coil-loop heat exchangers. (15th January 2016)
- Main Title:
- Optimum design of horizontal ground-coupled heat pump systems using spiral-coil-loop heat exchangers
- Authors:
- Go, Gyu-Hyun
Lee, Seung-Rae
Yoon, Seok
Kim, Min-Jun - Abstract:
- Highlights: Optimum design of horizontal ground heat pump systems is presented. Accuracy of numerical model is verified through indoor thermal response tests. A total of 160 parametric studies are conducted using numerical simulation models. Heat efficiencies are compared for 160 major combinations of design factors. Optimum design conditions are suggested using several economic analysis tools. Abstract: This paper deals with an optimum design of horizontal ground heat pump systems for spiral-coil-loop heat exchangers. A three dimensional numerical analysis model simulating the thermal behavior of a horizontal spiral-coil-loop heat exchanger was developed, and the accuracy of the model was verified through indoor thermal response tests. After that, a total of 160 parametric studies were conducted using numerical simulation models in order to grasp the degree of effects that key input parameters used in the model would have on the output. Then, an optimum design condition for horizontal ground coupled heat pump system was suggested using several economic analysis tools. Economic analysis factors, such as internal rate of return, savings to investment ratio, and simple payback period, show that certain design conditions (coil pitch: 0.08 m, setting depth: 2.5 m, circulating fluid velocity: 0.7 m s −1 ) provide the most economic feasibility. However, this condition also varies with the unit cost of operation and initial investment.
- Is Part Of:
- Applied energy. Volume 162(2016)
- Journal:
- Applied energy
- Issue:
- Volume 162(2016)
- Issue Display:
- Volume 162, Issue 2016 (2016)
- Year:
- 2016
- Volume:
- 162
- Issue:
- 2016
- Issue Sort Value:
- 2016-0162-2016-0000
- Page Start:
- 330
- Page End:
- 345
- Publication Date:
- 2016-01-15
- Subjects:
- Horizontal ground heat exchanger -- Thermal response test -- Numerical simulation -- Parametric studies -- Optimum design
Power (Mechanics) -- Periodicals
Energy conservation -- Periodicals
Energy conversion -- Periodicals
621.042 - Journal URLs:
- http://www.sciencedirect.com/science/journal/03062619 ↗
http://www.elsevier.com/journals ↗ - DOI:
- 10.1016/j.apenergy.2015.10.113 ↗
- Languages:
- English
- ISSNs:
- 0306-2619
- Deposit Type:
- Legaldeposit
- View Content:
- Available online (eLD content is only available in our Reading Rooms) ↗
- Physical Locations:
- British Library DSC - 1572.300000
British Library DSC - BLDSS-3PM
British Library HMNTS - ELD Digital store - Ingest File:
- 2254.xml